Technical Question |
How to make RS232 Comm. between PLC and Xpanel |
|
|
|
Follow simple instruction.
CICON
Channel 1 : RS232
PLC Parameter -> Channel1
Make the same 'Station No.' and ' Comm Parameters' both PLC and Xpanel.
Xpanel Designer
COM1 : RS232
I/O Devices -> New Device -> Serial Device -> Communication Port -> Station.
Device Type : KDT Systems CIMON-PLC HMI
Make the same 'Station No.' and ' Comm Parameters' both PLC and Xpanel.
RS232 PLCS with Xpanel.zip |
|
|
| 17 |
Technical Question |
How to make RS485 Comm. between PLC and Xpanel |
|
|
|
Follow simple instruction.
CICON
Channel 2 : RS485
PLC Parameter -> Channel2
Make the same 'Station No.' and ' Comm Parameters' both PLC and Xpanel.
Xpanel Designer
COM2 : RS485
I/O Devices -> New Device -> Serial Device -> Communication Port -> Station.
Device Type : KDT Systems CIMON-PLC HMI
Make the same 'Station No.' and ' Comm Parameters' both PLC and Xpanel.
RS485connection.zip |
|
|
| 16 |
Technical Question |
[SCADA]How to set up CimonX environment |
|
|
|
Please download vedio file to get idea how to set up CimonX environment.
All you have to do is that follow simple instruction.
|
|
|
| 15 |
Technical Question |
PLCS : How to Firmware upgrade |
|
|
|
Movie Download Please download video file for simple instruction.
Warning
Do not remove PLC from USB port until upgrade is finished.
|
|
|
| 14 |
Technical Question |
Xpanel Designer : How to write Hebrew and Arab language |
|
|
|
Movie Download Xpanel Designer V.2.15 supply Hebrew and Arab language display on Xpanel.
Pleaes download 'Xpanel Designer V.2.15' at download menu and see instruction video as attached file.
Hebrew and Arab language do not work with Simulator.
However, please check your project after downloading to Xpanel.
You can see your project is working properly at Xpanel screen.
* Font must be 'Microsoft Sans Serif' of Arab and Hebrew font.
|
|
|
| 13 |
Technical Question |
[Xpanel] How can I 'write the value to Omron PLC'? |
|
|
|
Omron PLC can be written when its mode is monitor. So you must change the mode to monitor.
Please set the value of DM6600 to 0101h. Even though the PLC power goes out, it remains to monitor mode. You can only change the DM6600 by program mode.
08_21.Xpanel QnA_081202_1E.pdf |
|
|
| 12 |
Technical Question |
[Xpanel] How to download the XPanel project data? |
|
|
|
There are three different methods to download the Xpanel project data as summarized here :
1. Via USB port (supporting models : which have the USB client port such as XT05MA, XT05SA, XT06CA, XT10CA, XT12CA) 2. Via Ethernet port (supporting models : which have the Ethernet port and needs OS version above V2.0) 3. Via removable storage (supporting models : which have the USB host or SD/MMC port and needs OS version above V2.0)
QnA_080118_1_XPanelLoader.pdf |
|
|
| 11 |
Technical Question |
[PLC] Is there any protocol over serial network to share data between two different PLC systems? |
|
|
|
| 10 |
Technical Question |
[TOUCH/PPC] How can I install or configure my software permanently on CIMON-TOUCH? |
|
|
|
The Enhanced Write Filter (EWF) protects the disk volume (“C:” volume) of CIMON-TOUCH/PPC
from all kinds of write access.
l When you setup your operating system, utility programs or change any file data on “C:”
volume, those changes will not be stored on “C:” disk directly but on the EWF volume.
l If you restart your TOUCH/PPC, the original data would be restored to the C: volume,
and you would lost all newly installed programs, system configurations and changes on files.
l If you want to save new data permanently, you have to execute the “EWF commit”
as shown in the following screen capture. Then the TOUCH/PPC will be restarted and the new data will be effective.
l After installing a program and its configuration, please execute the ' EWF commit'
Otherwise all new program setups will be lost.
l If there is any change in operation system configuration, please execute the 'EWF commit'.
Otherwise all new program setups will be lost.
l After creating new files or folders, please execute 'EWF commit'.
Otherwise all new program setups will be lost.
08_1.TOUCH QnA_081111_1_EWF.pdf |
|
|
| 9 |
Technical Question |
[XPANEL]How can I export/import the XPanel¡¯s TAG DB to/from Microsoft Excel or other 3rd. vender programs? |
|
|
|
The XPanelDesigner does not have a special menu for TAG DB exporting and importing. However, the clipboard function of Windows can be used for the same purpose. Use the “Copy” function of “Edit” menu while the TAG DB window is opened and some of TAGs in DB are under selected state. And next, activate the Microsoft Excel, and use the “Paste” function of “Edit” menu. Following table can be helpful to edit each TAG data in Excel worksheet.
QnA_070831_1_.zip |
|
|